4,407 Internet-Facing Industrial Controllers Expose U.S. Water Utilities to Attacks

A new report has identified 4,407 internet-facing Rockwell Automation/Allen-Bradley controllers exposing port 44818 (EtherNet/IP), with 65% located in the United States, as coordinated attacks disrupt water systems across at least 12 states.

The findings come from Forescout Research Vedere Labs, published August 5, 2026, following a wave of incidents that began in Minnesota in late July.

On July 28, Minnesota IT Services reported a coordinated cyberattack against more than 30 water systems statewide. Plymouth, South St. Paul, Maple Plain, and Braham confirmed operational impacts.

4,407 Internet-Facing Industrial Controllers

Braham reported that malware delivered via a wireless connection shut down water plant controls, while Plymouth’s affected equipment (two water towers and 14 sewer lift stations) was connected via cellular.

Two days later, the FBI and EPA issued a joint advisory confirming similar incidents across Michigan, South Dakota, and Georgia, with nine systems affected in Michigan and one wastewater lift station in South Dakota.

Threat actors targeted MicroLogix 1100 and 1400 PLCs, in some cases modifying controller logic or remotely changing IP addresses and passwords, causing loss of monitoring and control, pressure loss, and flooding risks that could allow untreated groundwater into drinking water pipes.

No attribution has been confirmed, though CISA had updated its advisory on Iranian-affiliated actors exploiting exposed PLCs just four days before the Minnesota incident.

Controllers with Exposed port 44818 (Source: Forescout )
Controllers with Exposed port 44818 (Source: Forescout)

Shodan queries on August 3 returned 4,407 devices exposing EtherNet/IP, with the U.S. (65%), Canada (12%), and Spain (3%) as top locations.

Over 70% of U.S.-based controllers are within large mobile carrier networks, connected via cellular routers that match the FBI/EPA advisory’s description.

MicroLogix 1400 accounts for 50% of exposed devices, followed by CompactLogix 1769 (22%), MicroLogix 1100 (8%), and ControlLogix 5590 (8%). Exposure has fallen 47% since March 2020’s peak of 7,814 devices, though it remains a persistent risk.

Among 22 hosts identified in cities hit by the current campaign, 86% shared a single mobile carrier network, and 15 devices in Eagan, Minnesota showed matching network addresses, firmware, and GPS coordinates suggesting a shared fleet.

No CVE has been confirmed to have been exploited in this campaign, but affected devices remain susceptible to known flaws.

CVE-2017-16740, a Modbus TCP denial-of-service bug, was the most prevalent, affecting 19 of 22 hosts in targeted cities, though exploitation requires Modbus TCP to be enabled, which was unconfirmed. Rockwell discontinued MicroLogix 1100 in 2022, leaving it without further patches.

Beyond controllers, researchers found expired certificates, abandoned remote-access hostnames, and forgotten servers tied to municipal utilities, including one certificate that has served only a default IIS page since 2019, pointing to incomplete asset inventories across the sector.

Mitigations

Forescout recommends blocking direct internet access to engineering protocols, restricting port 44818 and Modbus TCP via allowlists, and moving cellular gateways to private APNs or VPNs.

Enforce MFA for remote access, upgrade or replace end-of-life MicroLogix devices, and audit all VPNs, certificates, and remote-service hostnames for abandoned infrastructure.